HVAC Wire Size, MCA and Breaker (MOCP) Sizing

Enter the compressor RLA and the other loads to see the minimum circuit ampacity (MCA), the maximum breaker (MOCP) and the minimum copper wire size. The calculator needs JavaScript; the tables are below. No account, nothing to install.

NEC Wire Gauge / MCA / MOCP

MCA = 1.25 × Compressor RLA + Other FLAs (NEC 440.32)

The calculator box needs JavaScript. MCA = 1.25 x compressor RLA + other FLAs, rounded to 0.1 A. MOCP = 1.75 x compressor RLA + other FLAs, then the first standard breaker size at or above it. The wire size is read from the MCA on the ladder below.

Assumptions: 75°C copper conductors, ≤3 current-carrying conductors in raceway, standard 30°C ambient basis (NEC Table 310.16 & 440.22).

Verify against the equipment's own nameplate MCA/MOCP if listed — nameplate always wins. Check local code.

Wire size ladder

MCAEst. min copper wire
Up to 15 A14 AWG
Up to 20 A12 AWG
Up to 30 A10 AWG
Up to 40 A8 AWG
Up to 55 A6 AWG
Up to 70 A4 AWG
Over 70 A3 AWG or larger

Standard breaker sizes used: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A.

MCA, breaker and wire by compressor RLA

Each cell is MCA in amps, then the MOCP breaker size in amps, then the minimum copper wire size, for the compressor RLA in the first column and the other loads (fan, pump) shown at the top. Assumptions: 75°C copper conductors, ≤3 current-carrying conductors in raceway, standard 30°C ambient basis (NEC Table 310.16 & 440.22). Check local code.

Compressor RLA (A)Other FLAs 0 A: MCA / breaker / wireOther FLAs 2 A: MCA / breaker / wireOther FLAs 5 A: MCA / breaker / wire
56.3 A / 15 A / 14 AWG8.3 A / 15 A / 14 AWG11.3 A / 15 A / 14 AWG
67.5 A / 15 A / 14 AWG9.5 A / 15 A / 14 AWG12.5 A / 20 A / 14 AWG
78.8 A / 15 A / 14 AWG10.8 A / 15 A / 14 AWG13.8 A / 20 A / 14 AWG
810 A / 15 A / 14 AWG12 A / 20 A / 14 AWG15 A / 20 A / 14 AWG
911.3 A / 20 A / 14 AWG13.3 A / 20 A / 14 AWG16.3 A / 25 A / 12 AWG
1012.5 A / 20 A / 14 AWG14.5 A / 20 A / 14 AWG17.5 A / 25 A / 12 AWG
1113.8 A / 20 A / 14 AWG15.8 A / 25 A / 12 AWG18.8 A / 25 A / 12 AWG
1215 A / 25 A / 14 AWG17 A / 25 A / 12 AWG20 A / 30 A / 12 AWG
1316.3 A / 25 A / 12 AWG18.3 A / 25 A / 12 AWG21.3 A / 30 A / 10 AWG
1417.5 A / 25 A / 12 AWG19.5 A / 30 A / 12 AWG22.5 A / 30 A / 10 AWG
1518.8 A / 30 A / 12 AWG20.8 A / 30 A / 10 AWG23.8 A / 35 A / 10 AWG
1620 A / 30 A / 12 AWG22 A / 30 A / 10 AWG25 A / 35 A / 10 AWG
1721.3 A / 30 A / 10 AWG23.3 A / 35 A / 10 AWG26.3 A / 35 A / 10 AWG
1822.5 A / 35 A / 10 AWG24.5 A / 35 A / 10 AWG27.5 A / 40 A / 10 AWG
1923.8 A / 35 A / 10 AWG25.8 A / 40 A / 10 AWG28.8 A / 40 A / 10 AWG
2025 A / 35 A / 10 AWG27 A / 40 A / 10 AWG30 A / 40 A / 10 AWG
2126.3 A / 40 A / 10 AWG28.3 A / 40 A / 10 AWG31.3 A / 45 A / 8 AWG
2227.5 A / 40 A / 10 AWG29.5 A / 45 A / 10 AWG32.5 A / 45 A / 8 AWG
2328.8 A / 45 A / 10 AWG30.8 A / 45 A / 8 AWG33.8 A / 50 A / 8 AWG
2430 A / 45 A / 10 AWG32 A / 45 A / 8 AWG35 A / 50 A / 8 AWG
2531.3 A / 45 A / 8 AWG33.3 A / 50 A / 8 AWG36.3 A / 50 A / 8 AWG
2632.5 A / 50 A / 8 AWG34.5 A / 50 A / 8 AWG37.5 A / 60 A / 8 AWG
2733.8 A / 50 A / 8 AWG35.8 A / 50 A / 8 AWG38.8 A / 60 A / 8 AWG
2835 A / 50 A / 8 AWG37 A / 60 A / 8 AWG40 A / 60 A / 8 AWG
2936.3 A / 60 A / 8 AWG38.3 A / 60 A / 8 AWG41.3 A / 60 A / 6 AWG
3037.5 A / 60 A / 8 AWG39.5 A / 60 A / 8 AWG42.5 A / 60 A / 6 AWG
3138.8 A / 60 A / 8 AWG40.8 A / 60 A / 6 AWG43.8 A / 60 A / 6 AWG
3240 A / 60 A / 8 AWG42 A / 60 A / 6 AWG45 A / 70 A / 6 AWG
3341.3 A / 60 A / 6 AWG43.3 A / 60 A / 6 AWG46.3 A / 70 A / 6 AWG
3442.5 A / 60 A / 6 AWG44.5 A / 70 A / 6 AWG47.5 A / 70 A / 6 AWG
3543.8 A / 70 A / 6 AWG45.8 A / 70 A / 6 AWG48.8 A / 70 A / 6 AWG
3645 A / 70 A / 6 AWG47 A / 70 A / 6 AWG50 A / 70 A / 6 AWG
3746.3 A / 70 A / 6 AWG48.3 A / 70 A / 6 AWG51.3 A / 70 A / 6 AWG
3847.5 A / 70 A / 6 AWG49.5 A / 70 A / 6 AWG52.5 A / 80 A / 6 AWG
3948.8 A / 70 A / 6 AWG50.8 A / 80 A / 6 AWG53.8 A / 80 A / 6 AWG
4050 A / 70 A / 6 AWG52 A / 80 A / 6 AWG55 A / 80 A / 6 AWG
4151.3 A / 80 A / 6 AWG53.3 A / 80 A / 6 AWG56.3 A / 80 A / 4 AWG
4252.5 A / 80 A / 6 AWG54.5 A / 80 A / 6 AWG57.5 A / 80 A / 4 AWG
4353.8 A / 80 A / 6 AWG55.8 A / 80 A / 4 AWG58.8 A / 90 A / 4 AWG
4455 A / 80 A / 6 AWG57 A / 80 A / 4 AWG60 A / 90 A / 4 AWG
4556.3 A / 80 A / 4 AWG58.3 A / 90 A / 4 AWG61.3 A / 90 A / 4 AWG
4657.5 A / 90 A / 4 AWG59.5 A / 90 A / 4 AWG62.5 A / 90 A / 4 AWG
4758.8 A / 90 A / 4 AWG60.8 A / 90 A / 4 AWG63.8 A / 90 A / 4 AWG
4860 A / 90 A / 4 AWG62 A / 90 A / 4 AWG65 A / 90 A / 4 AWG
4961.3 A / 90 A / 4 AWG63.3 A / 90 A / 4 AWG66.3 A / 100 A / 4 AWG
5062.5 A / 90 A / 4 AWG64.5 A / 90 A / 4 AWG67.5 A / 100 A / 4 AWG
5163.8 A / 90 A / 4 AWG65.8 A / 100 A / 4 AWG68.8 A / 100 A / 4 AWG
5265 A / 100 A / 4 AWG67 A / 100 A / 4 AWG70 A / 100 A / 4 AWG
5366.3 A / 100 A / 4 AWG68.3 A / 100 A / 4 AWG71.3 A / 100 A / 3 AWG or larger
5467.5 A / 100 A / 4 AWG69.5 A / 100 A / 4 AWG72.5 A / 100 A / 3 AWG or larger
5568.8 A / 100 A / 4 AWG70.8 A / 100 A / 3 AWG or larger73.8 A / 110 A / 3 AWG or larger
5670 A / 100 A / 4 AWG72 A / 100 A / 3 AWG or larger75 A / 110 A / 3 AWG or larger
5771.3 A / 100 A / 3 AWG or larger73.3 A / 110 A / 3 AWG or larger76.3 A / 110 A / 3 AWG or larger
5872.5 A / 110 A / 3 AWG or larger74.5 A / 110 A / 3 AWG or larger77.5 A / 110 A / 3 AWG or larger
5973.8 A / 110 A / 3 AWG or larger75.8 A / 110 A / 3 AWG or larger78.8 A / 110 A / 3 AWG or larger
6075 A / 110 A / 3 AWG or larger77 A / 110 A / 3 AWG or larger80 A / 110 A / 3 AWG or larger

Frequently asked questions

What is MCA on an HVAC nameplate?

MCA is the minimum circuit ampacity: the smallest current rating the supply wiring to the unit must have. This page works it out as 1.25 times the compressor RLA plus the other full-load amps (fan, pump), the rule the Equipment Tracker app uses (NEC 440.32). If the equipment nameplate lists an MCA, the nameplate value is the one to use.

What is MOCP and how is the breaker size picked?

MOCP is the maximum overcurrent protection: the largest breaker or fuse the unit may be on. This page takes 1.75 times the compressor RLA plus the other full-load amps and then picks the first standard breaker size at or above that number. The standard sizes on the page are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175 and 200 amps. If the nameplate lists a maximum breaker size, use the nameplate.

What wire size does the page give for a given MCA?

It reads the MCA against a ladder of copper wire sizes: up to 15 A is 14 AWG, up to 20 A is 12 AWG, up to 30 A is 10 AWG, up to 40 A is 8 AWG, up to 55 A is 6 AWG, up to 70 A is 4 AWG, and above 70 A the page says 3 AWG or larger. It is an estimate of the minimum copper wire size, not a design.

What does this page assume?

Copper conductors rated 75 degrees C, no more than three current-carrying conductors in the raceway, and a standard 30 degrees C ambient (the basis of NEC Table 310.16 and 440.22). Aluminum wire, a hotter ambient, more conductors in the conduit, long runs and voltage drop all change the answer and are not covered. Check local code and the equipment nameplate.

Does the nameplate override this page?

Yes. If the equipment lists its own MCA and maximum breaker size on the nameplate, the nameplate always wins. This page is a quick reference for when you only have the compressor RLA and the other loads.

Is this a code compliance check?

No. It is a calculation aid built from the figures the Equipment Tracker app uses. Local electrical code and the authority having jurisdiction decide what is allowed, so check local code before you size or replace wiring or a breaker.

Does this page store anything or need an account?

No to both. The calculator runs in your browser and nothing is saved when you close the tab. If you want the equipment, its electrical details and service history kept on each unit, that is what Equipment Tracker is for.